Overview

Electrical grounding is a commonly misunderstood and improperly implemented component of environmental monitoring systems. Systems that do not use electrical grounding components can experience either complete system failures or intermittent problems that are hard to diagnose. However, just using grounding devices is not enough. Improper installation of electrical grounding components can render the components ineffective. Installing a system with the proper grounding equipment and following proper installation guidelines can reduce potential down time as well as costly repairs to system electronics.

Why implement grounding protection?

Most data loggers and sensors are made from delicate silicon chips such as microprocessors and other integrated circuitry. This equipment can become easily damaged by transient voltages such as power surges and spikes. These surges and spikes can cause permanent damage, like how a nearby lightning strike can burn electronics and wires. They may also cause small latent failures that erode equipment and cause permanent damage over time. These small latent failures are the most troublesome failures to diagnose because it appears as if the electronics just simply failed one day, when in fact the system had been prone to continuous intermittent power surges and spikes, continually eroding its performance.

Implementing proper grounding techniques not only protects from damaging surges and spikes, but more importantly keeps a system from experiencing the ill effects of latent system failures.

What causes power surges and spikes?

Voltage surges and spikes that damage the circuitry of data loggers and sensors travel through the easiest access point: cables that go into and out of the data logger. These cables can be the wires bringing in sensor signals or the RF coaxial cable or telephone wires bringing in telemetry communication. These power surges and spikes are most commonly caused by:

1. Lightning
2. Other Electrical Systems
3. Electrostatic discharge (ESD)

Lightning

Lightning is the most commonly thought of power surge or spike that damages electronic devices.

Lightning can damage a system in two ways: a direct strike, or through transient voltage surges that travel from the direct strike into nearby areas. Nothing can prevent damage from a direct lightning strike. When installing systems in lightning prone areas or where telemetry poles or antennas are located at higher elevations than their surroundings, lightning rods should be installed. Lightning rods do not attract lightning; they simply divert lightning strikes from causing direct-strike damage to nearby areas. Surge protection devices can then protect against the damaging surges traveling from the direct strike. As with all surge devices, lightning rods must be properly grounded to be effective. More information is detailed below in the Installation section.

While it may seem rare that a lightning strike would occur, it is more common than one would think. Damage from lightning strikes traveling through telephone lines, or RF coax cables occurs frequently and ruins data loggers, sensors, and telemetry modems. Additionally, surges can cause latent unexpected failures that bring down the system during at a later time.

Other Electrical Systems

Surges can come from within a building or facility from such things as fax machines, copiers, air conditioners, elevators, and/or motors/pumps, to name a few. These devices typically run on high AC voltages. It is best to keep environmental data logging equipment, including sensor cables, away from such devices, as signals generated from electric motors induce large noises into the signal.

Electrostatic discharge (ESD)

Electrostatic discharge, called ESD, is caused by rubbing two non-conducting materials together. This causes electrons to transfer from one non-conducting material to another. ESD is the shock caused by touching a doorknob after shuffling across a carpet. This ESD is typically in excess of 10kV (10,000 Volts) and can be very damaging to sensitive electronics. Most, if not all, data loggers and sensors on the market today have built in ESD protection to protect them when being handled. Additionally it is rare that a circuit board will have to be handled directly when installing and maintaining an environmental data logging system. However, care should always be taken when handling electronic circuitry to avoid discharge. This can be achieved by using a grounding strap, touching a metal object to discharge any built up electrons before handling circuitry, and avoiding working on a carpet while handling circuit boards.

How Surge Protection Devices (SPDs) work

Lightning and surge protection devices work by routing voltage surges and spikes away from the electrical components they are protecting and dispersing it to a ground plane, such as the earth or a copper pipe inside of a building. Every grounding system therefore consists of two main components: the protection device that routes the damaging signals and the ground connection the signals are routed to. It is important that both components are in place and properly utilized. One without the other, or one properly implemented with the other improperly implemented, is the same as no surge protection system at all.

Types of Protection Devices

There are several areas of protection for environmental monitoring devices such as:

– The incoming power from a battery or DC voltage source
– AC surge protection
– Wireless transmission cables, such coaxial cables used for radio, cellular, or satellite telemetry
– Telephone lines if using landline telephone telemetry
– Sensor input protection

Power Line Protection

Fuses are typically one-time-use devices that protect from voltage or current overloads as well as short circuits from an environmental monitoring system power source. Fuses consist of a housingcontaining a metal wire that will melt when heated by a preset electrical current, called the breaking capacity. This prevents the electrical surge from reaching sensitive electronics to which the fuse is connected.

Fuses should be selected based on:

– The breaking capacity rating, which for any fuse should be selected just above the maximum expected current of the system
– The voltage level of the system and the voltage rating of the fuse
– Fuse packaging. Fuses come in many standard sizes and types such as glass cartridges, plug-in, etc. Pick the packaging that is supported by your equipment

Other fuse-type protections such as circuit breakers or resettable fuses exist but are not commonly used. Circuit breakers are better for large currents as found in AC power, as opposed to the DC voltages in environmental systems. Resettable fuses are several times more expensive than standard fuses, which are common in environmental monitoring systems.

AC surge protectors

An AC surge protection device will limit the effect of surges through the AC power lines on expensive monitoring equipment. An AC surge protection device can be as simple as ones purchased at department stores for use in homes. Note that power supplies are much wider than a simple AC power cable and can cover more than one slot on a typical surge protector.

Protection can also be obtained from AC to DC power supplies or AC battery chargers. AC to DC power supplies come in two varieties: switching and transforming power supplies. Switching power supplies are small, lightweight and inexpensive as they use integrated circuits to convert AC to DC power. Transforming power supplies are typically bulkier, heavier, and more expensive than switching power supplies since they use a large coil of wire called a transformer to convert AC to DC power. However, transforming power supplies are usually more rugged and offer good protection to monitoring systems. If the AC power spikes, it would cause damage to equipment connected to it, but a transforming power supply will short and only damage itself, protecting the equipment it is powering. A switching power supply on the other hand, unless listed as a specification, may send damaging voltages onto the system it is powering.

Note: When purchasing an AC surge protection device is that it should be UL 1449 rated. This rating is given by the Underwriters Laboratory and means that the device has been tested for surge suppression. It also indicates the device is compliant with the 1998 thermal fusing standards, which means it will shut off power during strong surges, ultimately keeping it from catching on fire.

Wireless Telemetry Protection

A few kinds of devices exist for the protection of wireless telemetry from radio, cellular or satellite signals. These include:

– Air gap arrestors
– Gas discharge tubes
– Power isolators

Note: When picking any wireless protection device, make sure the device is rated for the frequency range your wireless device is operating. For example, a spread spectrum license-free radio may operate from 902 MHz to 928 MHz. A wireless protection device used with that telemetry should therefore be used with that system.

Air gap lightning arrestors are by far the least expensive, as well as the least protecting, of wireless telemetry protection devices. Originally designed to protect old tube-style TVs, these devices do not offer enough protection for the heavily microprocessor-based devices used today. They are better than no protection at all, but are not as reliable or as well designed to protect against surges and spikes as other wireless telemetry protectors.

Gas discharge tubes are typically the next least expensive. They protect equipment from surges at high frequency ranges, and are the most common protection for wireless transmission equipment.

Power isolators are much more expensive but provide the most effective protection. Power isolators use a special kind of ferrite to transfer high-frequency wireless signals over a magnetic field instead of a physical connection.

Telephone Line Protection

According to the National Electric Code (Article 800-32), all surge protectors connected to landline telephone communications lines must be UL tested and listed. It may be against local, state and/or national building codes to install certain non-listed protectors on a premise. Installing a non-UL listed landline telephone protector could make the installer liable in case of a fire.

Telephone line surge protection is a necessity for any telephone telemetry monitoring system. While this may seem unnecessary since telephones typically do not have external surge protection, modems are more prone to surges than telephones. Modems have more delicate electronics in them and are usually connected to expensive equipment. A damaging surge through a modem can and will potentially damage electronics to which it is connected.

Installation

As mentioned before, the connection to a ground plane is as important as the surge protection device itself. Following proper installation techniques and attaching to proper grounding planes is required for a workable electrical grounding system.

Grounding Material Selection

There are three main parts to any grounding system after the protection device: The grounding plane, the grounding wire, and the bond between them.

The grounding plane:

1. The best grounding planes are:
a. Copper or copper clad ground rods driven into the earth
b. Copper water pipes or other building grounds, such as metal structural frame
c.  Metal enclosures and casings (which in turn should be grounded to earth ground)

2. Grounding rods should be either copper or galvanized steel, and have a minimum diameter of 5/8 inch.

3. Aluminum should not be used in direct soil burial as a grounding rod since the alkalinity of the soil will etch the metal. This causes disconnection and an increase in impendence between the grounding system and earth ground.

The grounding wire:

1. Use heavy wire gauges (10 AWG or larger) for running the grounding wire. This is important as a thicker wire gauge, along with a short cable, runs the impendence of the grounding wire lower, keeping voltage drops during surges to a minimum.

2. The cable can be either solid or stranded (just as long as it is a heavy-enough wire gauge). The wire can be either bare or insulated.

The bond between them:

1. The use of dissimilar metals for connection from the surge protection device to the grounding plane should be avoided. Over time the connection can wear down and cause undesirable effects on the grounding system as the connection will degrade due to the oxidized layers that form between them.

2. Ground wires should be bonded to the grounding plane (such as grounding rod or copper water pipes) using grounding clamps. Be sure to pick a clamp that matches the size of either the rod or pipe.

3. Both copper and aluminum are UL-approved for use in grounding protection systems. However, copper is a better conductor of electricity and can be used in smaller gauges.

Proper Installation Guidelines:

1. Do not sharply bend the surge protection wires during termination. Offer a straight path to ground.
2. Keep the surge protection wires as short as possible to improve effectiveness and response time.
3. Keep the surge protection device a few feet away from the protected equipment to allow enough response time for the transient voltage to be suppressed.
4. Ensure all systems connect to the same grounding point only once. Multi paths to a ground plan create different voltage potentials on the system that can result in transient surges. This simply means only pound one copper rod in the earth for grounding.

References

http://www.ul.com/consumers/surge.html
http://www.isa.org/
http://www.littelfuse.com/data/en/Product_Catalogs/EC101-J_V052505.pdf
http://www.ul.com/lightning/

REV: 13G18

Comments

  1. Chris Winters

    I had no idea that silicon chips were used in ground protection technology. I happen to live in an area that experiences a lot of lighting storms and I’ve always wondered how they protect the city. I wonder how often the grounding equipment needs to be replaced.

  2. David Peacock

    You may want to edit the words: “The breaking capacity rating, which for any fuse should be selected just above the maximum expected current of the system”. You seem to be confusing the “current rating” of the fuse (which is the normal “headline rating” of a fuse) with the “breaking capacity”, which is the maximum current which the fuse can safely break without ruptering or exploding, and is normally many times higher than the “current rating”.

  3. Ali serdar

    Hello. My question is; Is it logical and trustworthy to connect the earthing ground to lightning ground ( franklin rod) then to ground rod? Yes the resistance between the grounding rod and the equipment is almost infinity and when lightning strikes, the surge will go thru the grounding rod. But because the amount of the current is too high, it will cause some spikes and aches within the equipment connected to grounding also. Then it will cause damage in the equipment eventyally. Is it more relaible to hammer grounding rods for earth grounding and grounding rods for lightning grounding in distant from each other? Thanks for your valuable answer in advance.

  4. Alex

    I have a relatively small storage shed (remote in my yard) that has a tin roof over steel and wood construction. I installed electrical in it that will rely on its own deep ground rod and I wanted to also add lightning protection.

    Question: can I tie the Ground copper wire from the electrical system to the same deep ground rod to be used for the Lightning protection system?

    Also, do I really need an ESD device in such case ?

    Thank you.

  5. faizan

    The Content shared over here is really beneficial as at some point of time , everyone faces these kind of problems in life . Thanks for sharing .

  6. Tim Wilson

    We are faced with multiple lighting strikes every year. We just had one at one of our teleports and the lighting arrest system seemed to work as there was no apparent physical & visible damage to the equipment and we did not lose power or see any disruption of AC power, However we experienced numerous RF and low voltage equipment failures and are scratching our heads to how this may have happened. We are thinking that there was transient power that the surge caused. One rack inside a shelter had multiple equipment failures. We caught the actual strike on video surveillance system and identify the exact location of the hit and there was no visual damage to any structure just the equipment. Any help in identifying the issues that contributed to the equipment failure would be helpful.

    1. Richard Woods

      Hey Tim

      Not sure if you ever got any feedback to this question. Regarding lightning strikes and low voltage damage.

      I am in IT and manage schools which are over a rather large surface area.

      What I’m finding with experience is most IT guys do not seem to factor in bonding. Not do the roofing/AC and other technical folk.

      I’m leaning toward experience when we are crossing distribution boards, eg a PC is on a different DB to the network switch, connected with copper LAN, where we use quality network cable, non cca Cat6 specifically it appears more likely on an overhead strike (not direct) we will find a network port on a pc or switch or both and sometimes a projector or display port has stopped working. (Projectors are often on adjacent circuits to pc)

      This becomes even more complicated where we have old cast iron gutter pipes where the old school sparkies did a fantastic job at bonding electrical outlets to every conceivable conductor. Often causing loops and surge damage.as an example on a 2nd floor the origional plug socket conduit is bonded to a cast iron pipe and we were finding the pc which was on the inside of the cast iron wall was notorious for popping power supplies or motherboard network ports. We installed a pcv insulated circuit…. and this problem. Went away.

      Hope this gives you some insight.