NexSens MCIL-8-MP Port Pinout


NexSens X2-SDLMC, X2-CBMC, and X3-SUB data loggers incorporate MCIL-8-MP plugs for connection of sensor cables with MCIL-8-FS plug connectors. The pinout for the sensor ports is as follows:

Figure 1: MCIL-8-MP pinout

Note: All splitter extensions contain the same pinout and signal configuration; however, only one 232 sensor can be connected to each splitter/port. The arrow on the 2-way splitter and the end port on the 4-way splitter indicates on which port the 232 sensor may be connected.

MCIL-8-MP Sensor Port Pin# Signal
1 RS232-Tx*
2 GND
3 RS232-Rx*
4
5 Power (12VDC)
6 SDI-12
7 RS-485B
8 RS-485A

*RS-232 transmit/recieve is labeled from the data logger’s perspective (should be wired to sensor’s receive/transmit, respectively).